OZD Profi 12M G12
Industrial Networking:FiberINTERFACES:Field Bus:Profibus Rail Repeaters
Description interface converter electrical/optical for PROFIBUS-field bus networks;
repeater function; for quartz glass FO; approval for Ex-zone 2 (Class 1, Div. 2)
Port type and quantity 2 x optical: 4 sockets BFOC 2.5 (STR)
1 x electrical: Sub-D 9-pin, female, pin assignment according to EN 50170 part 1
Type OZD Profi 12M G12
Order No. 943 727-321
Electrical interface
Signal type PROFIBUS (DP-V0, DP-V1, DP-V2 und FMS)
Bit rate 9.6; 19.2; 45.45; 93.75; 187.5; 500 kbit/s;
1.5; 3; 6; 12 Mbit/s (automatic setting)
Signal delay time (optional input/output) <= 6.5 bit times
Input/output signal RS 485 level
Input voltage range -7 V ... +12 V
Galvanic isolation no
Optical interface
Wavelength 860 nm
Cascadibility not limited
More Interfaces
Power supply 5-pin terminal block, screw mounting
Signaling contact 5-pin terminal block, screw mounting
Measuring outputs "Optical input power" 2 mm sockets
Network size - length of cable
Single mode fiber (SM)9/125 μm -
Multimode fiber (MM) 50/125 μm 3000 m
13 dB link budget at 860 nm; A = 3 dB/km, 3 dB reserve
Multimode fiber (MM) 62.5/125 μm 3000 m
15 dB link budget at 860 nm; A = 3.5 dB/km, 3 dB reserve
Multimode fiber HCS (MM) 200/230 μm 1000 m
18 dB link budget at 860 nm; A = 8 dB/km, 3 dB reserve
Multimode fiber POF (MM) 980/1000 μm -
Power requirements
Operating voltage 18 ... 32 VDC, typ. 24 VDC
Galvanic isolation yes
Current consumption max. 200 mA
Power consumption 4.8 W
Output voltage/output current (pin6) 5 VDC +5%, -10%, short circuit-proof/90 mA
Redundancy
Redundancy functions HIPER-Ring (ring structure), redundant 24 V infeed
Ambient conditions
Operating temperature 0 ºC to +60 ºC
Storage/transport temperature -40 ºC to +70 ºC
Relative humidity <95% (non-condensing)
Mechanical construction
Dimensions (W x H x D) 40 x 140 x 77.5 mm
Mounting DIN rail or mounting plate
Weight 500 g
Protection class IP 40
page 1 of 2
Housing material die-cast zink
Approvals
Issued or requested approvals FM Class 1, Div. 2; C-Tick; according to directive 94/9/EG (ATEX 95): Ex II 3 G
(Zone 2)
Scope of delivery and accessories
Scope of delivery device, start-up instructions
Accessories to order separately manual, order no. 039 629-001
page